| Significant corrosion of conductors and bus bar. Notice the green copper wires. | Over-filled and open junction within attic. A larger closed box is needed. | |
![]() |
![]() |
|
| Haphazard light fixture installation by bedroom clothes closet shelf. A significant fire hazard. | Insulation of one wire (second down from top) extending into terminal prevents proper contact. | |
![]() |
![]() |
|
| Extensive overheating of terminals and conductors. | Significant overheating of neutral conductor (top). Terminal connection is loose. | |
![]() |
![]() |
|
| Improper multiple conductor connection to lower terminal of circuit breaker. This terminal is suitable for only one wire. | Inadequate splice of grounding conductors. Loosely twisted together. |